ZigBee performance in 400 kv air insulated power substation

Q. Shan, I.A. Glover, P.J. Moore, I. Portugues, R. Rutherford, R.C. Atkinson, Shahzad Ahmed Bhatti, Robin J. Watson, Magued Iskander (Editor), Vikram Kapila (Editor), Mohammad A. Karim (Editor)

Research output: Chapter in Book/Report/Conference proceedingChapter

Abstract

An experimental assessment of the impact of the electromagnetic environment of a 400 kV substation on the performance of ZigBee equipment is described. The experimental assessment includes a pragmatic field trial and a laboratory test. The laboratory test, in which all external noise and interference are excluded, is used as a control. A simple set of metrics are used to compare the performance of ZigBee equipment deployed in the substation with that deployed in a controlled laboratory environment. The results based on more than 1.6 Gbit of transmitted data show no significant adverse impact of the substation electromagnetic environment on the performance of ZigBee equipment.
Original languageEnglish
Title of host publicationTechnological Developments in Education and Automation
PublisherSpringer
Pages15-18
Number of pages4
ISBN (Print)9789048136551
DOIs
Publication statusPublished - Dec 2008

Keywords

  • ZigBee
  • partial discharge
  • power substations

Fingerprint

Dive into the research topics of 'ZigBee performance in 400 kv air insulated power substation'. Together they form a unique fingerprint.