UHF and IEC60270 correlation analysis of radiated frequency band measurements on resin insulation void samples

B.G. Stewart, A.J. Reid, M.D. Judd, R.A. Fouracre

Research output: Contribution to conferencePaper

6 Citations (Scopus)

Abstract

Partial discharge (PD) measurement is an established condition monitoring technique used to assess the deterioration of high voltage insulation systems such as power transformers and gas-insulated switchgear. Two popular monitoring techniques employ radiated RF measurements and conventional apparent charge measurements according to the IEC60270 Standard. Recent research has shown that combining simultaneous radiated RF with IEC60270 measurements of PD events appears to provide additional information to assist in the discrimination of specific insulation faults. This paper aims to show for sample voids in resin that the frequency content of the radiated RF signals can be used as an additional discriminatory feature for simultaneous RF and IEC60270 measurements in identifying PD produced by single and multiple resin voids under electrical stress.
Original languageEnglish
Pages138-141
Number of pages4
DOIs
Publication statusPublished - 2007
EventElectrical Insulation Conference and Electrical Manufacturing Expo - Nashville, Tennessee , United States
Duration: 24 Sept 200727 Sept 2007

Conference

ConferenceElectrical Insulation Conference and Electrical Manufacturing Expo
Abbreviated titleEIC/EME
Country/TerritoryUnited States
CityNashville, Tennessee
Period24/09/0727/09/07

Keywords

  • electrical insulation
  • charge measurement
  • gas insulation
  • frequency measurement