Abstract
In this paper, the stability studies for different wind farm collection network topologies have been performed. As the wind farm becomes larger, the inter-array network becomes larger.so that the impedance of the overall system will be increased. This means that the inter-array configuration can impact the stability of system. The dynamic studies results presented in this paper show that the star collection network topology has the ability to be connected to weaker grid followed by radial, double sided and single side ring collection network topology.
Original language | English |
---|---|
Title of host publication | 5th IET International Conference on Renewable Power Generation |
Place of Publication | Stevenage |
Publication status | Published - 21 Sep 2016 |
Event | 5th IET International Conference on Renewable Power Generation (RPG) 2016 - IET London: Savoy Place, London, United Kingdom Duration: 21 Sep 2016 → 23 Sep 2016 http://conferences.theiet.org/rpg-europe/about/index.cfm |
Conference
Conference | 5th IET International Conference on Renewable Power Generation (RPG) 2016 |
---|---|
Country/Territory | United Kingdom |
City | London |
Period | 21/09/16 → 23/09/16 |
Internet address |
Keywords
- vector current control
- wind farm
- AC collection network
- stability
- weak grid
- inter-array network