Abstract
A simulation investigation is conducted for high frequency current transformers (HFCT) partial discharge (PD) detection on a grounding conductor in a medium voltage (MV) switchgear compartment. A three-dimensional (3-D) bus bar chamber of an air insulated MV metal clad switchgear including PD sources and grounding position is developed using Comsol Multiphysics. The PD sources are placed at different locations in the chamber and the sensitivity of the HFCT signal is investigated depending of different position of the bus bar chamber grounding. The current induced by PD in the grounding conductor is provided as input to the HFCT sensor. Throughout the simulation it can be seen that there is an influence on the sensitivity of the HFCT signal depending on the grounding position. The analysis helps also to inform the nature of HFCT signals related to different PD locations and grounding wire positions which will help to refine and understand better HFCT measurements for condition monitoring within such systems.
| Original language | English |
|---|---|
| Title of host publication | 2022 IEEE Electrical Insulation Conference, EIC 2022 |
| Place of Publication | Piscataway, NJ. |
| Publisher | IEEE |
| Pages | 162-165 |
| Number of pages | 4 |
| ISBN (Electronic) | 9781665480239 |
| ISBN (Print) | 9781665480246 |
| DOIs | |
| Publication status | Published - 19 Jun 2022 |
| Event | 40th IEEE Electrical Insulation Conference 2022 - Knoxville Convention Center, Knoxville, United States Duration: 19 Jun 2022 → 23 Jun 2022 https://ieee-eic.org/ |
Publication series
| Name | 2022 IEEE Electrical Insulation Conference, EIC 2022 |
|---|
Conference
| Conference | 40th IEEE Electrical Insulation Conference 2022 |
|---|---|
| Abbreviated title | EIC 2022 |
| Country/Territory | United States |
| City | Knoxville |
| Period | 19/06/22 → 23/06/22 |
| Internet address |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 9 Industry, Innovation, and Infrastructure
Keywords
- bus bar chamber
- partial discharge
- high frequency current transformer
- finite element method
- grounding conductor
Fingerprint
Dive into the research topics of 'Simulation of HFCT PD detection in MV bus bar chamber'. Together they form a unique fingerprint.-
Simulation of PD RF EM wave propagation in different MV bus bar compartment configurations
Miljanović, M., Kearns, M. & Stewart, B. G., 21 Jun 2024, 23rd International Symposium on High Voltage Engineering (ISH 2023). 46 ed. Piscataway, NJ: IEEE, Vol. 2023. p. 692-698 7 p. (IET Conference Proceedings).Research output: Chapter in Book/Report/Conference proceeding › Conference contribution book
Open AccessFile13 Downloads (Pure) -
Simulation of PD RF propagation in MV bus bar chambers
Miljanovic, M., Kearns, M. & Stewart, B. G., 1 Feb 2024, 2023 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP). IEEE, p. 1-4 4 p. (2023 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP)).Research output: Chapter in Book/Report/Conference proceeding › Conference contribution book
Open AccessFile -
Temperature distribution simulation in an MV switchgear bus bar chamber
Miljanovic, M., Kearns, M. & Stewart, B. G., 30 Oct 2022, p. 1-4. 4 p.Research output: Contribution to conference › Paper › peer-review
Open AccessFile
Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver