Protection performance assessment with grid-forming converter acting as reference generator during black-start

Eleni Tsotsopoulou, Dimitrios Tzelepis, Agusti Alvarez, Neil Miller, Adam Dysko

Research output: Contribution to conferencePaperpeer-review

29 Downloads (Pure)

Abstract

The studies presented in this paper aim to assess the operation of existing protective schemes (i.e. overcurrent protection) within UK networks, considering black-start scenario initiated from converter-based distributed energy sources. The primary objective is to investigate whether it is realistically feasible for a converter-based battery storage unit, to replace a synchronous generator in black-start scenarios, and deliver the same benefits accounting for adequate fault levels and reliable protection operation. The case studies include transmission and distribution level (11kV up to 400kV) fault level calculations and assessment of the protection performance under balanced/unbalanced faults considering existing settings proposed for such black-start conditions.
Furthermore, the utilization of a voltage-controlled overcurrent protection scheme is investigated as a potential protection solution, to address the reduced fault levels resulting from the converter-based source. The results and observations aim to build a solid foundation for the design of protection schemes during black-start scenarios within distribution systems.
Original languageEnglish
Number of pages6
Publication statusPublished - 8 Mar 2022
EventConference: 16th International Conference on Developments in Power System Protection. - UK, Newcastle, United Kingdom
Duration: 7 Mar 202210 Mar 2022
Conference number: 16
https://dpsp.theiet.org/

Conference

ConferenceConference: 16th International Conference on Developments in Power System Protection.
Abbreviated titleDPSP
Country/TerritoryUnited Kingdom
CityNewcastle
Period7/03/2210/03/22
Internet address

Keywords

  • grid-forming converter
  • black-start
  • overcurrent protection

Fingerprint

Dive into the research topics of 'Protection performance assessment with grid-forming converter acting as reference generator during black-start'. Together they form a unique fingerprint.