Research output: Contribution to journal › Article › peer-review
During AC series arc faults (SAFs), arcing current features can change or vanish under different conditions. The phenomena make it challenging to detect SAFs. To address the issues, this paper presents a detection model based on regular coupling features (RCFs). After the model is only trained by the samples in single-load circuits, it can detect SAFs under unknown multi-load circuits. To extract RCFs, asymmetric magnetic flux is coupled by passing the live line and the neutral line through the current transformer. According to the unique signals, two time-domain features and one frequency-domain feature are extracted to represent RCFs, including impulse -factor analysis, covariance-matrix analysis and multiple frequency-band analysis. Then, the impulse factor and its threshold are used to preprocess the signals and decrease analysis complexity for the classifier. Finally, the experimental results show that the proposed method has significantly improved generalization ability and detection accuracy in SAF detection.
| Original language | English |
|---|---|
| Pages (from-to) | 2761-2771 |
| Number of pages | 11 |
| Journal | IEEE Transactions on Industrial Informatics |
| Volume | 19 |
| Issue number | 3 |
| Early online date | 23 Feb 2022 |
| DOIs | |
| Publication status | Published - 23 Feb 2022 |