Implications of fault current limitation for electrical distribution networks

S.M. Blair, A.J. Roscoe, C.D. Booth, G.M. Burt, A. Teo, C.G. Bright

Research output: Chapter in Book/Report/Conference proceedingConference contribution book

6 Citations (Scopus)

Abstract

This paper explores the potential future need for fault current limitation in the UK's power system, and some of the technical implications of this change. It is estimated that approximately 300-400 distribution substations will require fault current limitation, based on the statistical analysis of the projected fault level "headroom" (or violation). The analysis uses a UK electrical system scenario that satisfies the Government's target for an 80% cut in CO2 emissions by 2050. A case study involving the connection of distributed generation (DG) via a superconducting fault current limiter (SFCL) is used to illustrate the potential protection and control issues. In particular, DG fault ride-through, autoreclosure schemes, and transformer inrush current can be problematic for SFCLs that require a recovery period. The potential solutions to these issues are discussed, such as the use of islanding or automation to reduce the fault level.
LanguageEnglish
Title of host publicationIET International Conference on Developments in Power System Protection (DPSP)
Subtitle of host publication(IET-DPSP 2010)
Number of pages5
DOIs
Publication statusPublished - Nov 2010

Fingerprint

Electric fault currents
Distributed power generation
Electric power distribution
Superconducting fault current limiters
Electric instrument transformers
Statistical methods
Automation
Recovery

Keywords

  • fault current limiter
  • power distribution
  • power transformers
  • substation protection

Cite this

Blair, S. M., Roscoe, A. J., Booth, C. D., Burt, G. M., Teo, A., & Bright, C. G. (2010). Implications of fault current limitation for electrical distribution networks. In IET International Conference on Developments in Power System Protection (DPSP): (IET-DPSP 2010) https://doi.org/10.1049/cp.2010.0355
Blair, S.M. ; Roscoe, A.J. ; Booth, C.D. ; Burt, G.M. ; Teo, A. ; Bright, C.G. / Implications of fault current limitation for electrical distribution networks. IET International Conference on Developments in Power System Protection (DPSP): (IET-DPSP 2010). 2010.
@inproceedings{054b8ad548d04a1e94090e2df53a0c0f,
title = "Implications of fault current limitation for electrical distribution networks",
abstract = "This paper explores the potential future need for fault current limitation in the UK's power system, and some of the technical implications of this change. It is estimated that approximately 300-400 distribution substations will require fault current limitation, based on the statistical analysis of the projected fault level {"}headroom{"} (or violation). The analysis uses a UK electrical system scenario that satisfies the Government's target for an 80{\%} cut in CO2 emissions by 2050. A case study involving the connection of distributed generation (DG) via a superconducting fault current limiter (SFCL) is used to illustrate the potential protection and control issues. In particular, DG fault ride-through, autoreclosure schemes, and transformer inrush current can be problematic for SFCLs that require a recovery period. The potential solutions to these issues are discussed, such as the use of islanding or automation to reduce the fault level.",
keywords = "fault current limiter, power distribution, power transformers, substation protection",
author = "S.M. Blair and A.J. Roscoe and C.D. Booth and G.M. Burt and A. Teo and C.G. Bright",
year = "2010",
month = "11",
doi = "10.1049/cp.2010.0355",
language = "English",
isbn = "978-1-84919-239-2",
booktitle = "IET International Conference on Developments in Power System Protection (DPSP)",

}

Blair, SM, Roscoe, AJ, Booth, CD, Burt, GM, Teo, A & Bright, CG 2010, Implications of fault current limitation for electrical distribution networks. in IET International Conference on Developments in Power System Protection (DPSP): (IET-DPSP 2010). https://doi.org/10.1049/cp.2010.0355

Implications of fault current limitation for electrical distribution networks. / Blair, S.M.; Roscoe, A.J.; Booth, C.D.; Burt, G.M.; Teo, A.; Bright, C.G.

IET International Conference on Developments in Power System Protection (DPSP): (IET-DPSP 2010). 2010.

Research output: Chapter in Book/Report/Conference proceedingConference contribution book

TY - GEN

T1 - Implications of fault current limitation for electrical distribution networks

AU - Blair, S.M.

AU - Roscoe, A.J.

AU - Booth, C.D.

AU - Burt, G.M.

AU - Teo, A.

AU - Bright, C.G.

PY - 2010/11

Y1 - 2010/11

N2 - This paper explores the potential future need for fault current limitation in the UK's power system, and some of the technical implications of this change. It is estimated that approximately 300-400 distribution substations will require fault current limitation, based on the statistical analysis of the projected fault level "headroom" (or violation). The analysis uses a UK electrical system scenario that satisfies the Government's target for an 80% cut in CO2 emissions by 2050. A case study involving the connection of distributed generation (DG) via a superconducting fault current limiter (SFCL) is used to illustrate the potential protection and control issues. In particular, DG fault ride-through, autoreclosure schemes, and transformer inrush current can be problematic for SFCLs that require a recovery period. The potential solutions to these issues are discussed, such as the use of islanding or automation to reduce the fault level.

AB - This paper explores the potential future need for fault current limitation in the UK's power system, and some of the technical implications of this change. It is estimated that approximately 300-400 distribution substations will require fault current limitation, based on the statistical analysis of the projected fault level "headroom" (or violation). The analysis uses a UK electrical system scenario that satisfies the Government's target for an 80% cut in CO2 emissions by 2050. A case study involving the connection of distributed generation (DG) via a superconducting fault current limiter (SFCL) is used to illustrate the potential protection and control issues. In particular, DG fault ride-through, autoreclosure schemes, and transformer inrush current can be problematic for SFCLs that require a recovery period. The potential solutions to these issues are discussed, such as the use of islanding or automation to reduce the fault level.

KW - fault current limiter

KW - power distribution

KW - power transformers

KW - substation protection

UR - http://www.scopus.com/inward/record.url?scp=77956329852&partnerID=8YFLogxK

U2 - 10.1049/cp.2010.0355

DO - 10.1049/cp.2010.0355

M3 - Conference contribution book

SN - 978-1-84919-239-2

BT - IET International Conference on Developments in Power System Protection (DPSP)

ER -

Blair SM, Roscoe AJ, Booth CD, Burt GM, Teo A, Bright CG. Implications of fault current limitation for electrical distribution networks. In IET International Conference on Developments in Power System Protection (DPSP): (IET-DPSP 2010). 2010 https://doi.org/10.1049/cp.2010.0355