Diagnostic potential of free-space radiometric partial discharge measurements

A. Jaber, P. Lazaridis, B. Saeed, P. Mather, M. F. Q. Vieira, R. Atkinson, C. Tachtatzis, E. Iorkyase, M. Judd, I. A. Glover

Research output: Chapter in Book/Report/Conference proceedingConference contribution book

2 Citations (Scopus)
25 Downloads (Pure)

Abstract

The work reported in this paper addresses the calibration of four types of partial discharge (PD) emulator required for the development of a PD Wireless Sensor Network (WSN). Three partial discharge (PD) emulators have been constructed: a floating-electrode emulator, and two internal PD emulators. Both DC and AC HV power supplies are used to initiate PD which is measured using concurrent free-space radiometry (FSR) and a galvanic contact method based on the IEC 60270 standard. A new method of estimating absolute PD activity level from a radiometric measurement is proposed.
Original languageEnglish
Title of host publication2017 XXXIInd General Assembly and Scientific Symposium of the International Union of Radio Science
Place of PublicationPiscataway, NJ
PublisherIEEE
Number of pages4
ISBN (Electronic)9789082598704
DOIs
Publication statusPublished - 13 Nov 2017
EventGeneral Assembly and Scientific Symposium of the International Union of Radio Science - Montreal, Canada
Duration: 19 Aug 201726 Aug 2017
Conference number: XXXII

Conference

ConferenceGeneral Assembly and Scientific Symposium of the International Union of Radio Science
Abbreviated titleURSI GASS
Country/TerritoryCanada
CityMontreal
Period19/08/1726/08/17

Keywords

  • partial discharge emulator
  • PD wireless sensor network
  • free-space radiometry

Fingerprint

Dive into the research topics of 'Diagnostic potential of free-space radiometric partial discharge measurements'. Together they form a unique fingerprint.

Cite this