Development and application of test cases for comparing vertical ground heat exchanger models

M. Bernier, M. Kummert, S. Bertagnolio

Research output: Contribution to conferencePaperpeer-review

6 Citations (Scopus)
228 Downloads (Pure)

Abstract

The main objective of this paper is to establish a set of test cases for analytical verifications and intermodel comparisons of ground heat exchanger (GHX) models used in building simulation programs. Several test cases are suggested. They range from steady-state heat rejection in a single borehole to varying hourly loads with large yearly thermal imbalance in multiple borehole configurations. The usefulness of the proposed test cases is illustrated by running them with different GHX models.This comparison exercise has shown that 1-D models compare favourably well with the more elaborate 3-D models for relatively small simulation periods. The cyclic heat rejection/collection test has revealed some small deficiency in the load aggregation scheme of a particular model. Finally, the use of the asymmetric (cooling-dominated) load profile test case for a bore field composed of 100 boreholes revealed that the borehole wall temperature predicted by two GHX models can differ by as much as 10oC after a 30 year simulation.
Original languageEnglish
Number of pages8
Publication statusPublished - 6 Sept 2007
EventInternational Building Performance Simulation Association (IBPSA) Conference 2007 - Beijing, China
Duration: 3 Sept 20076 Sept 2007

Conference

ConferenceInternational Building Performance Simulation Association (IBPSA) Conference 2007
CityBeijing, China
Period3/09/076/09/07

Keywords

  • modeling
  • ground heat exchanger
  • simulations
  • test cases
  • heat pumps

Fingerprint

Dive into the research topics of 'Development and application of test cases for comparing vertical ground heat exchanger models'. Together they form a unique fingerprint.