Abstract
An automated transformer dissolved gas analysis evaluation system based on the recently released IEEE Standard C57.104-2019 for mineral oil-immersed transformers is implemented and its outputs demonstrated. The system includes diagnostic capabilities using the Duval Triangles 1-4-5 and Rogers Ratio method. In addition, a Health Index derived from the above Standards is proposed as a compact, yet informative metric for tracking transformer health. Finally, some of the challenges in developing such an implementation are highlighted.
Original language | English |
---|---|
Title of host publication | 2020 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP) |
Place of Publication | Piscataway, NJ. |
Publisher | IEEE |
Pages | 1-4 |
Number of pages | 4 |
ISBN (Print) | 9781728195735 |
DOIs | |
Publication status | Published - 18 Oct 2020 |
Event | Annual Conference on Electrical Insulation and Dielectric Phenomena (2020) : CEIDP 2020 - On-line, United States Duration: 18 Oct 2020 → 30 Oct 2020 http://www.ceidp.org http://ceidp.org http://www.ceidp.org http://ceidp.org |
Conference
Conference | Annual Conference on Electrical Insulation and Dielectric Phenomena (2020) : CEIDP 2020 |
---|---|
Abbreviated title | CEIDP |
Country/Territory | United States |
Period | 18/10/20 → 30/10/20 |
Internet address |
Keywords
- transformers
- condition monitoring
- dissolved gas analysis
- DGA
- C57.104