Abstract
This paper analyzes the behavior of a Voltage Source Converter Based HVDC system under DC cable fault conditions. The behavior of the HVDC system during a permanent line-to-earth fault is analyzed, outlining the systems configuration and behavior at each stage of the fault timeline. Operation of the proposed system under a single earthing configurations, i.e. Converter (solid) earthed/AC transformer unearthed, was analyzed and simulated, with particular attention paid to the converters operation. It was observed that the development of potential earth loops within the system as a result of DC line-to-earth faults leads to substantial overcurrent and results in system configuration oscillation.
Original language | English |
---|---|
Pages (from-to) | 459 - 464 |
Number of pages | 6 |
Journal | 39th Annual Conference of the IEEE Industrial Electronics Society IECON 2013 |
DOIs | |
Publication status | Published - Nov 2013 |
Event | IEEE IECON 2013 - Vienna, Austria Duration: 28 Oct 2013 → … |
Keywords
- HVDC power convertors
- HVDC power transmission
- earthing
- power cables
- power transmission faults
- single earthing configurations