Abstract

Communication assisted transfer trip schemes are generally preferred for transmission lines to provide reliable and accelerated protection from both ends. Dependability of such schemes on the performance of conventional distance and/or directional relays at both ends expresses a concern on their reliability in power systems with high penetration of converter-interfaced renewable sources. This work demonstrates the impact of converter-based sources on the available accelerated protection schemes and proposes a new transfer trip scheme mitigating the issue. The proposed method includes a new criteria to identify the fault direction in converter-dominated power networks using local voltage and current data. The scheme is tested for a modified WSCC 9-bus system with 100% converter-interfaced renewable penetration using PSCAD/ EMTDC and found to be reliable for different faults and system conditions.
Original languageEnglish
Number of pages4
DOIs
Publication statusPublished - 19 Dec 2022
Event22nd National Power Systems Conference (NPSC) - IIT Delhi, Delhi, India
Duration: 17 Dec 202219 Dec 2022
Conference number: 57038
https://npsc2022.com/

Conference

Conference22nd National Power Systems Conference (NPSC)
Country/TerritoryIndia
CityDelhi
Period17/12/2219/12/22
Internet address

Keywords

  • accelerated protection
  • transfer trip scheme
  • distance relaying
  • directional relaying
  • power system faults
  • converter-interfaced renewable sources

Fingerprint

Dive into the research topics of 'A reliable accelerated protection scheme for converter-dominated power networks'. Together they form a unique fingerprint.

Cite this