A low-loss hybrid bypass for DC fault protection of modular multilevel converters

I. A. Gowaid

Research output: Contribution to journalArticle

25 Citations (Scopus)
172 Downloads (Pure)

Abstract

Without additional circuitry, the half-bridge modular multilevel converter (HB-MMC) is endangered under dc side faults. Typically, a bypass thyristor is augmented to each HB cell to take up fault current until ac circuit breakers interrupt the dc fault. This paper proposes a dc fault protection concept for HB-MMC stations that requires insignificant extra silicon area relative to the thyristor bypass concept. Herein, bypass thyristors of typical HB cells are rearranged such that an independent modular shadow rectifier bridge (SRB) is formed. A low-loss switch assembly is utilized to immediately isolate the MMC following fault detection and the SRB suppresses the fault current by injecting a reverse dc voltage. Among several advantages, the proposed arrangement incurs insignificant losses in steady state, and the MMC is capable of operating in STATCOM mode briefly after fault inception to support ac grid voltage. The proposed concept may be suitable for clearing temporary faults on overhead HVDC lines. Several structural variations will be viewed and discussed. Applicability for twolevel VSC will be addressed. The concept is validated by detailed numerical simulations of a ±200kV HB-MMC station under dc fault.
Original languageEnglish
Number of pages10
JournalIEEE Transactions on Power Delivery
Early online date5 Apr 2016
DOIs
Publication statusE-pub ahead of print - 5 Apr 2016

Keywords

  • DC fault
  • modular multilevel converter
  • MMC
  • HVDC
  • DC fault protection
  • power electronic converters

Fingerprint Dive into the research topics of 'A low-loss hybrid bypass for DC fault protection of modular multilevel converters'. Together they form a unique fingerprint.

  • Cite this