A coordinated multi-element current differential protection scheme for active distribution systems

Vassilis C. Nikolaidis, George Michaloudis, Aristotelis M. Tsimtsios, Dimitrios Tzelepis, Campbell David Booth

Research output: Contribution to journalArticlepeer-review

17 Citations (Scopus)
39 Downloads (Pure)

Abstract

This paper introduces a current differential protection scheme, appropriate for application in medium voltage active distribution systems, where it is desired to keep the greatest possible number of loads and DG units energized during a fault. Conventional two-terminal percentage current differential relays are used to form successive, time-current-coordinated, differential protection zones. Multiple time-delayed differential elements in each protection zone guarantee coordination with the zone’s lateral protection devices, as well as between successive differential protection zones. Sensitive time-delayed differential elements protect against relatively high-resistance faults, while instantaneous differential elements minimize protection speed whenever possible. Additional emergency differential elements deal with post-fault topology changes and breaker failure conditions enhancing the overall scheme's performance. The proposed scheme is applied to a model of real medium voltage distribution system with distributed generation, considering a ring topology operation. A detailed simulation-based study proves the applicability and enhanced performance of the proposed scheme.
Original languageEnglish
Pages (from-to)4261-4271
Number of pages11
JournalIEEE Transactions on Power Delivery
Volume37
Issue number5
DOIs
Publication statusPublished - 4 Feb 2022

Keywords

  • differential protection
  • distributed generation
  • percentage differential relay
  • power distribution systems
  • protection coordination
  • relays
  • circuit faults
  • reliability
  • current measurement
  • topology
  • power distibution
  • medium voltage

Fingerprint

Dive into the research topics of 'A coordinated multi-element current differential protection scheme for active distribution systems'. Together they form a unique fingerprint.

Cite this